Product Features
How The System Works
R32 Monoblock Heat Pump for House Heating, Cooling & Daily Hot Water Supply
Sunrain R32 Monoblock air to water heat pumps, with self-developed Controllers and Full DC Inverters, are designed to bring comfort with daily hot water, house heating, and cooling. Our R32 Monobloc Air to Water Heat Pumps come with a smart controller, ERP A+++ energy rating, low noise operation, R32 refrigerant, smart control, and intelligent defrosting. Moreover, these cost-effective inverter heat pumps are highlighted with a 5-inch colorful touch screen, -25°C EVI low ambient temperature operation, and a click remote software update.
Model | BLN-006TC1 | BLN-012TC1 | BLN-018TC1 | BLN-012TC3 | BLN-018TC3 | ||
Rated voltage / Frequency | 220-240V~ / 50Hz | 380-415V/3N~/50Hz | |||||
Heating¹ | Capacity | kW | 2.92-9.10 | 4.30-15.20 | 7.24-21.90 | 4.30-15.20 | 7.24-21.90 |
Input Power | kW | 0.61-2.11 | 0.87-3.73 | 1.50-5.88 | 0.87-3.73 | 1.50-5.88 | |
Input Current | A | 2.80-9.25 | 4.02-16.38 | 6.86-30.25 | 1.78-6.04 | 2.82-9.16 | |
Heating² | Capacity | kW | 2.99-8.16 | 4.25-14.55 | 6.36-19.45 | 4.25-14.55 | 6.36-19.45 |
Input Power | kW | 1.03-2.92 | 1.45-4.28 | 2.15-6.85 | 1.45-4.28 | 2.15-6.85 | |
Input Current | A | 4.57-12.79 | 6.71-18.80 | 9.84-30.12 | 2.84-6.78 | 3.71-10.60 | |
Cooling | Capacity | kW | 1.38-5.70 | 3.65-11.04 | 4.55-17.20 | 3.65-11.04 | 4.55-17.20 |
Input Power | kW | 0.67-2.44 | 1.12-3.97 | 1.85-7.31 | 1.12-3.97 | 1.85-7.31 | |
Input Current | A | 3.06-10.27 | 5.18-17.44 | 8.47-32.1 | 1.97-6.30 | 2.99-11.26 | |
SCOP (Water Temp. At 35ºC) | 4.98 | 4.90 | 4.91 | 4.90 | 4.93 | ||
SCOP (Water Temp. At 55ºC) | 3.84 | 3.86 | 3.94 | 3.86 | 3.93 | ||
Rated Input Power | kW | 3.5 | 5.40 | 7.50 | 5.85 | 10.5 | |
Rated Input Current | A | 15.0 | 25.0 | 35.0 | 10.0 | 17.0 | |
Refrigerant Type/Charge/GWP | .../kg | R290/0.55/3 | R290/0.90/3 | R290/1.4/3 | R290/0.90/3 | R290/1.4/3 | |
CO2 Equivalent | / | 0.0017t | 0.0027t | 0.0042t | 0.0027t | 0.0042t | |
Operation Pressure(Low Side) | MPa | 0.8 | 0.8 | 0.8 | 0.8 | 0.8 | |
Operation Pressure(High Side) | MPa | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | |
Maximum Allowable Pressure | MPa | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | |
Electrical Shockproof | / | I | I | I | I | I | |
IP Class | / | IPX4 | IPX4 | IPX4 | IPX4 | IPX4 | |
Max. Outlet Water Temp. | ºC | 75 | 75 | 75 | 75 | 75 | |
Operating Ambient Temp | ºC | -25~45 | -25~45 | -25~45 | -25~45 | -25~45 | |
Water Piping Connections | inch | G1 | G1 | G1-1/4 | G1 | G1-1/4 | |
Rated Water Flow | m³/h | 1.0 | 2.06 | 3.10 | 2.06 | 3.1 | |
Water Pressure Drop | kPa | 20 | 20 | 55 | 20 | 55 | |
Min/Max Water Pressure | MPa | 0.1/0.3 | 0.1/0.3 | 0.1/0.3 | 0.1/0.3 | 0.1/0.3 | |
Noise Level | dB(A) | 48 | 50 | 55 | 50 | 55 | |
Net Dimensions ( L×W×H ) | mm | 1187×418×805 | 1287×448×904 | 1187×488×1456 | 1287×448×904 | 1187×488×1456 | |
Net Weight | kg | 110 | 123 | 184 | 123 | 184 | |
Rated Test Conditions: Heating¹: Ambient Temp 7ºC/6ºC(DB/WB),Water-In/Out Temp 30ºC/35ºC Heating²: Ambient Temp 7ºC/6ºC(DB/WB),Water-In/Out Temp 47ºC/55ºC Cooling: Ambient Temp 35ºC/24ºC(DB/WB),Water-In/Out Temp 12ºC/7ºC |